PVC Cable

H05VV-F Wire Suppliers in UAE

PVC Cable Specification

 

Verified Manufacturer

Verified Manufacturer (Contact directly for instant quote)

PVC Cable Specification

Temprature Voltage Size
-15° C to + 70° C or + 85° C in HR PVC Up to 1100 V. 1.50 SQMM & 2.50 SQMM UPTO 61 CORE
Min. Bending Radius Insulation resistance Conductor
7 x cable diameter Min. 20 MΩ x km
  • 99.99% oxygen free copper
  • tin plated copper
Marking Packaging Features
1 to 90 M.   Sequential Marking on Cable 500 / 1000 meters on drums
  • Special heat resistant insulation
  • High current carrying capacity
  • Less heat energy radiation
  • Longer flex life
Nominal Voltage Operating Temprature Test Voltage
  • H05VV-F : 300/500 V
  • H05V2V2-F : 300/500 V
  • H05VV-F -20°c to +80°C
  • H05V2V2-F -20°c to +90°C
  • H05VV-F : 2.5KV
  • H05V2V2-F : 2.5KV
Standards Color Code Insulation
  • BS EN 50525-2-11
  • IEC 60227-5 SANS 1574
  • VDE 0281-5
  • 2 Core – Black, Red
  • 3 Core – Yellow, Red, Blue
  • 4 Core – Black, Yellow, Red, Blue
  • 5 Core – Black, Yellow, Red, Blue, Grey
  • HO5VVF :PVC
  • HO5V2V2F: Heat Resistant PVC

 

H05VV-F Wire up to +80°C and H05V2V2-F Heat Resistant PVC Cable up to +90°C temperature

Tempratue Range Of H05V2V2-F Cables

Operating Temprature
  • H05VV-F: -20°c to +80°C
  • H05V2V2-F: -20°c to +90°C

PVC Flexible Wires in Single & Multi Core at Lowest Price in Dubai

H05VV-F Wire Technical Dimensions

H05VV-F (300/500 V)
Nominal insulation thickness Min insulation resistance at 70°C Nominal cross sectional area of conductor Nominal sheath thickness in mm Max overall diameter in mm Max conductor resistance at 20°C
5 core 3 core 2 core 4 core 2 core 3 core 4 core 5 core
Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit
mm MΩkm sqmm mm mm mm mm mm mm mm mm mm mm mm mm Ω/km
0.80 0.010 2.50 1.20 1.00 1.00 1.10 10.60 8.40 11.40 09.20 12.50 10.10 13.90 11.20 07.98
0.60 0.010 1.00 0.90 0.80 0.80 0.90 07.50 5.90 08.00 06.30 09.00 07.10 09.80 07.80 19.50
0.60 0.011 0.75 0.90 0.80 0.80 0.80 07.20 5.70 07.60 06.00 08.30 06.60 09.30 07.40 26.00
0.70 0.010 1.50 1.10 0.90 0.80 1.00 08.60 6.80 09.40 07.40 10.50 08.40 11.60 09.30 13.30
0.80 0.008 4.00 1.40 1.20 1.10 1.20 12.10 9.70 13.10 10.50 14.30 11.50 16.10 13.00 04.95

 

H05V2V2-F (300/500 V)
Nominal insulation thickness Max conductor resistance at 20°C Nominal cross sectional area of conductor Nominal sheath thickness in mm Max overall diameter in mm Min insulation resistance at 90°C
2 core 3 core 4 core 5 core 2 core 3 core 4 core 5 core
Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit Upper limit Lower limit
mm Ω/km sqmm mm mm mm mm mm mm mm mm mm mm mm mm MΩkm
0.80 07.98 2.50 1.00 1.00 1.10 1.20 10.60 8.40 11.40 09.20 12.50 10.10 13.90 11.20 0.010
0.60 19.50 1.00 0.80 0.80 0.90 0.90 07.50 5.90 08.00 06.30 09.00 07.10 09.80 07.80 0.010
0.60 26.00 0.75 0.80 0.80 0.80 0.90 07.20 5.70 07.60 06.00 08.30 06.60 09.30 07.40 0.011
0.70 13.30 1.50 0.80 0.90 1.00 1.10 08.60 6.80 09.40 07.40 10.50 08.40 11.60 09.30 0.010
0.80 04.95 4.00 1.10 1.20 1.20 1.40 12.10 9.70 13.10 10.50 14.30 11.50 16.10 13.00 0.008

 

PVC Flexible wires Size Chart

Thickness of
PVC Insulation
(Nom.)
mm
No. of Cores
& Cross Sectional Area
NO x mm2
Thickness of
Innersheath (min.)
Extruded
mm
STRIP ARMOURED  CABLE Standard Delivery
Length in
Mtrs.
WIRE ARMOURED  CABLE Current Rating
Strip
Size

mm

Approx. Net
weight of Cable
Kg / km
Approx. OD

mm

Thickness of
PVC Outer sheath
(Min) mm
Thickness of
PVC Outer sheath
(Min) mm
Approx. OD

mm

Round Wire
Dia mm
Approx. Net
Weight of Cable
Kg / Km
In Air/ Duct.

Amps

Direct in
Ground Amps
0.80 2 x 1.5 0.30 1000 1.24 13.60 1.40 415 20 23
0.80 3 x 1.5 0.30 1000 1.24 14.10 1.40 430 17 21
0.80 4 x 1.5 0.30 1000 1.24 15.00 1.40 490 17 21
0.80 5 x 1.5 0.30 1000 1.24 15.90 1.40 545 14 16
0.80 6 x 1.5 0.30 1000 1.24 16.90 1.40 605 13 15
0.80 7 x 1.5 0.30 1000 1.24 16.90 1.40 630 13 14
0.80 10 x 1.5 0.30 1000 1.40 20.60 1.40 835 11 13
0.80 12 x 1.5 0.30 4 x 0.8 760 19.50 1.24 1000 1.40 21.50 1.60 950 10 12
0.80 14 x 1.5 0.30 4 x 0.8 830 20.80 1.40 1000 1.40 22.40 1.60 1040 10 11
0.80 16 x 1.5 0.30 4 x 0.8 920 21.70 1.40 1000 1.40 23.30 1.60 1130 9 11
0.80 19 x 1.5 0.30 4 x 0.8 1040 23.10 1.40 1000 1.40 24.70 1.60 1265 9 10
0.80 24 x 1.5 0.30 4 x 0.8 1250 26.40 1.40 1000 1.40 28.00 1.60 1510 8 9
0.80 27 x 1.5 0.30 4 x 0.8 1355 26.90 1.40 1000 1.40 28.50 1.60 1610 8 9
0.80 30 x 1.5 0.30 4 x 0.8 1430 27.80 1.40 1000 1.40 29.40 1.60 1700 7 9
0.80 37 x 1.5 0.30 4 x 0.8 1670 29.70 1.40 1000 1.40 31.30 1.60 1960 7 8
0.90 2 x 2.5 0.30 1000 1.24 14.80 1.40 500 27 32
0.90 3 x 2.5 0.30 1000 1.24 15.40 1.40 520 24 27
0.90 4 x 2.5 0.30 1000 1.24 16.40 1.40 590 24 27
0.90 5 x 2.5 0.30 1000 1.24 17.50 1.40 660 19 23
0.90 6 x 2.5 0.30 1000 1.24 18.70 1.40 745 18 21
0.90 7 x 2.5 0.30 1000 1.24 18.70 1.40 780 17 20
0.90 10 x 2.5 0.30 4 x 0.8 900 21.8 1.4 1000 1.40 23.40 1.60 1110 15 18
0.90 12 x 2.5 0.30 4 x 0.8 1020 22.8 1.4 1000 1.40 24.40 1.60 1240 14 17
0.90 14 x 2.5 0.30 4 x 0.8 1130 23.8 1.4 1000 1.40 25.40 1.60 1340 13 16
0.90 16 x 2.5 0.30 4 x 0.8 1210 24.9 1.4 1000 1.40 26.50 1.60 1455 13 15
0.90 19 x 2.5 0.30 4 x 0.8 1355 26.1 1.4 1000 1.40 27.70 1.60 1605 12 14
0.90 24 x 2.5 0.30 4 x 0.8 1655 30 1.4 1000 1.56 32.00 1.60 1970 11 13
0.90 27 x 2.5 0.30 4 x 0.8 1770 30.6 1.4 1000 1.56 32.60 1.60 2100 10 12
0.90 30 x 2.5 0.30 4 x 0.8 1940 32 1.56 1000 1.56 33.60 1.60 2250 10 12
0.90 37 x 2.5 0.40 4 x 0.8 2300 34.7 1.56 1000 1.56 37.10 2.00 2900 9 11

 

Manufacturer of PVC Control and Power Cables in Copper & Aluminium Conductors

Conductor Size of PVC Insulated Wire

Conductor Size mm2 No.and Diameter of Wires No/mm
10.0 7/1.35
1.5 1/1.38
1.0 1/1.13
2.5 1/1.78
25.0 7/2.14
16.0 7/1.70
35.0 9/1.53

 

PVC (Polyvinyl Chloride) Sheathed Cables & Electrical Wire in 300V/ 500V / 1100V

PVC Sheathed Cables Voltage Rating

Nominal voltage :
  • H05VV-F : 300/500 V
  • H05V2V2-F : 300/500 V
Test voltage :
  • H05VV-F : 2.5KV
  • H05V2V2-F : 2.5KV

 

Most Common Types Of PVC Coated Cables

H05VV-F Cable

H05VV-F Cable

H05V2V2-F Heat Resistant PVC Cable s

H05V2V2-F Heat Resistant PVC Cable

PVC Flexible Wiress

PVC Flexible Wires

PVC Control Cabless

PVC Control Cables

PVC Power Cables

PVC Power Cables

Polyvinyl Chloride Sheathed Cables

Polyvinyl Chloride Sheathed Cables

PVC Armoured Cables

PVC Armoured Cables

PVC Electrical Wire

PVC Electrical Wire

 

PVC Wire Application

Application overview
Tri-rated cable Switchgear and panel wire manufactured to CSA, UL and British Standard
Twin & Earth cable (624Y) Mains electricity wiring
218Y cable  (H03VV-F) Domestic and office power supply
2491X cable (H05V-K / H07V-K) Flexible panel wire
309Y cable (H05V2V2-F) Portable tools power supply
2192Y cable (H03VVH2-F) General wiring in public areas
318A cable (Arctic grade) Low temperature resistant power supply
318Y cable (H05VV-F) Domestic appliance power supply
Twinflex cable Battery cable
6381Y cable Power, lighting and internal wiring cable. Also suitable for AC and DC telecommunications applications.
Elevator flatform cable For lifts and elevators

 

PVC Cable vs XLPE Cable

Factor PVC Cable XLPE Cable
Installation Easy to Install Slightly Tougher to Install
Electric Load Suitable for Regular Loads Suitable for Greater Loads
Chemical Resistance Good Very Good
Heat Resistance Average Good
Cost Saving High Cost Compare to XLPE Insulated Cable Low Cost Compare to PVC Insulated Cable
Short Circuit Temp. 160 Degrees C 250 degrees C
Maximum Operating Temp. 70 Degrees C 90 degrees C
Lower Operating Temperature -15°C for General Purpose Compounds -400 C for XLPE Grade.
Toughness Good Poor Compare to PVC
Health Toxic Neutral